Honeywell Pro 3000 User Manual

Honeywell Pro 3000 User Manual

Description Same Business Day Fast Shipping! • The TH3110D1008 Honeywell PRO 3000 Non-Programmable Thermostat is a customer favorite! • Everyone loves the clear Backlit display! • This thermostat is a single stage heat and cool thermostat which can be used on conventional Gas, Oil, Electric, Heat Pump, Forced Warm Air, Hot Water, 750 Millivolt, Steam or Gravity heating systems. • You can use the supplied battery for power or the thermostat or the thermostat can be hardwired. • The wiring terminal hookups are labeled: Rc, R, W, Y, G, O, B and C. • This is a manual change over thermostat.

• This thermostat comes with an installation book and with batteries. Sony Cd Architect 5 2 Crack Heads. • We have the thermostat’s Features and Technical Specifications listed below.

We also have a picture with an option for your to purchase. • Please email us at anytime if you have a question. Our email address is: • We would love to help you out and have your business!

Appliance manuals and free pdf instructions. Find the user manual you need for your home appliance products and more at ManualsOnline.

Below we have three PDF file links that show the TH3110D1008 Honeywell PRO 3000 Non-Programmable Thermostat’s promotional literature, operating maual and installation guide: We hope these links will be useful to you. Honeywell PRO 3000 Thermostat.

Honeywell Pro 3000 User Manual

The Honeywell VISTA-20P is an alarm control panel and a member of the Honeywell VISTA Series of security systems. This workhorse of a panel has been around for a very long time, once being under known as the ADEMCO VISTA 20P. While the VISTA-20P is considered a residential alarm control panel, it is certainly equipped with enough features to be used in commercial settings as well. The VISTA-20P consists of a circuit board installed inside of a metal alarm cabinet. You can connect alarm keypads, hardwired alarm devices, wireless receivers, alarm sirens, etc.

To the alarm control panel’s circuit board to customize your Honeywell home security system. Unlike the self-contained wireless alarm control panels such as the or, the VISTA-20P alarm control panel does need to be paired with at least (1) alarm keypad to control your home security system.

The Honeywell VISTA-20P alarm control panel supports up to (48) total zones of protection. There are (8) hardwired zones built into the alarm control panel itself. Using the zone doubling feature, you can expand those (8) zones up to a total of (15) zones. You can also add wired or wireless expansion modules to expand the total number of zones.

When upgraded with a, you can add up to (40) wireless zones using any of the Honeywell 5800 Series wireless devices for a total of (48) zones of protection. You can also use hardwired zone expanders, like the Honeywell, if you would like to use up to (48) wired zones. In addition to the (48) possible zones, you can also program up to (16) wireless key fob buttons which do not take up any of the protection zones. Zone 1 on the VISTA-20P is setup as a fire protection zone and supports up to (16) two-wire smoke detectors but can also be reprogrammed for any other zone type as well. The Honeywell VISTA-20P is also partitionable and features (2) partitions which can protect (2) independent areas.

There is also an optional 3rd partition called a common partition. You are able to arm either partition, or both, while leaving the common area disarmed so that you have access to the other partitions. The Honeywell VISTA-20P is controlled by wired alarm keypads and you can add up to (8) console keypads such as the,,. In addition to the (8) console keypads, you can also add up to (4) touchscreen keypads, including the or using the (4) AUI device addresses. We do not recommend using an AUI touchscreen keypad to program your Honeywell VISTA-20P. In fact, a fixed English console keypad such as the is not recommended for alarm control panel programming either as you will not be able to navigate the *56 zone programming menus. Alarm Grid suggests at least one alphanumeric alarm keypad such as the to be installed with your VISTA-20P for full programming access.

The is an ideal addition to a VISTA-20P alarm control panel as it upgrades the VISTA-20P with (40) available wireless zones and provides access to the advanced programming menus using a single device. The Honeywell alarm control panel is powered by an included plug-in 120VAC transformer (Honeywell 1321) which must be wired to terminals 1 and 2 on the VISTA-20P alarm control panel’s terminal strip. Terminals 4 and 5 provide auxiliary power (up to a maximum of 12VDC, 600mA) for powering devices like keypads, motion detectors, glass break detectors, etc.

Terminals 3 and 4 supply up to 12VDC, 2AMP alarm output for compatible sounders. When a burglar alarm is tripped, the VISTA-20P uses a steady output and when a fire alarm is tripped, a temporal pulse is used. A rechargeable sealed lead-acid type battery can also be used to provide backup power during power outages. You must use at least a 12VDC, 4AH backup battery which should provide up to (24) hours of backup power. You can use terminals 21-24 to wire a traditional phone line to your Honeywell VISTA-20P if you want phone line alarm monitoring for your alarm control panel. As more and more security system owners are getting rid of their home telephones, the VISTA-20P is also compatible with the AlarmNet alternative alarm monitoring communicators.

Add the for internet alarm monitoring, the or for dual path monitoring which uses both internet and cellular GSM communications. I'm a long time Vista user, since the Vista 5. I was delighted to hear the Vista 20 can now interface to my Ericsson T-68i as i have already implemented a voice command system, eg, when i say ' Office' or ' Control Room' (sometimes i have to say these commands twice) the T-68i runs and internal batch file on the sub-processor and engages the software functions to work accordingly. Do you think there will be a code release to interface the Vista 20 to my automated dog feeding setup?

Essentially its a set of macros that run server-side and enable windows core services to allow machine code, that in turn enables virtual relays & I/O to lift a flap on the dog food container, once my pet comes within proximity range ( 15-30cm) of the embedded receiver on his bowl. I look forward to Honeywells response. Thanks, Jason Cleary. Just powered down and was able to enter Installer mode. Have no idea what happend. Funny my field is computer networks and I just want to go back through the logs to see what happen.:). I did see that my TUX had the wrong time yeaterday and set it.

It asked if I wanted the time on the panel set too and I said yes. Wondering if something there messed it up. Yeah I don't want to even look at *88 to see what it's set to.

Will be switching to you com as soon as my contract is up. Appreciate all the helpful info you provide. Yes, *98 would be the lockout exit mode, and depending on how your monitoring company has set field *88, it may have locked you out of using the code + 800 AND also locked you out of the backdoor method. It also may have been unlocked remotely by them as that certainly is possible. We've also heard of many people accidentally exiting with *98 when they meant to do *99. At this point, it sounds like you'll have to hope your monitoring company is going to do the right thing and allow you access back into the panel programming.

How much longer do you have on your contract? After entering my Installer code and 800 I receive a long beep and then nothing happens. Entering the wrong code and 800 does nothing. About to power off and on the system but wanted to see if anyone knew what the issue may be. I know I am using the correct IC however I did enter it incorrectly a few times prior (no beep) and then had to go look at my notes and verified what I had set it to.

After verifying I am now getting a long beep. Will the system lock you out if the wrong code is entered too many times for a period of time? Hi, I installed a vista 20p and a hardwired Honeywell Aurora PIR motion sensor. I hooked up the wires in the sensor from left to right as follows: RED,BLACK,GREEN,WHITE. And in the panel as follows: BLACK to screw #4, RED to screw #5, GREEN with 2000 ohm resistor to screw #17 and WHITE to screw 16 (ground). I then enable it in my 6160 Honeywell keypad to Zone Type 04 Interior Follower. But it now reads Zone 6 Faulted on my keypad.

I have no idea why and can't figure out why it's doing this. Any suggestions would be appreciated.

That zone is an End of Line resistor. (All our zones are that.) It is zone 8. You are correct on the back (against house) and front (cover) for the tamper switches. It is the one for the cover that seems bad. Pressing the button in to simulate closing the cover shows intermittent connectivity, so hopefully that is what is wrong.

The system worked for about 20 years before we started getting failures on that zone with the system not armed. (I.e., this is not a new installation that I've messed up.) That's what led me to suspect the board rather than switch or wiring - it was giving us failures (not fault) when the system was not armed. We'd get a fast series of beeps and the panel would tell us that Zone 8 had a failure. With that switch physically bypassed (actually both tamper switches - I shorted across that lead in the panel box) the system works fine. Other than replacing the tamper switch I can't think of anything to try. There can be a lot of variables in the situation you describe in paragraph one.

Is that zone using an End of Line Resistor? It also may make a difference which zone number it is, for example, tolerance for resistance is lower on zone 1 than on other zones in the 20P family of panels. If there are 2 tamper switches on the bell, I assume one is for the cover, and the other is for the back of the unit, where it mounts to the wall, and since you say they're in series, I assume they are normally closed, any idea which tamper it is you're having the issue with?

I would say no, to your question, if the tamper switch is changing state from good to bad, then it should show good, then bad on the system. I don't understand the electronics behind the zone switches. I've one zone with 4 items in series. That zone gives a failure regularly even when the system is not armed. Open a door and the zone should fault - fine.

Close everything and it should be ready to arm - fine. But apparently the zone is neither faulted (switch open) or good (all switches closed). I can't figure out what a switch can be if not open or closed. I've traced it to the outside bell.

Inside there are two tamper switches connected in series. One of the switches seems intermittent based on holding a meter to the terminals and operating the switch.

Is the system smart enough to know if a switch is intermittent to flag a failure? Assuming I just need to replace a tamper switch, where's the best place to get one? Yes, check 100 means the panel thinks you have RF expansion, so it expects to see a receiver set to address 00 (Check 1 + address, in this case, Check 100). If you don't have RF on the system, and you didn't program any zones with an RF, UR, or BR input type (03, 04, or 05) then it could be the RF House Code in *24. In panel programming, press *24 then 00, 00, 00, you should hear a triple beep after the last 0, then *99 and see if the check 100 returns. If it does, you have to have a zone in there somewhere with a wireless input type. The 20HW was a non-addressable panel, meaning the keypads would all be set to address 31, and would work.

I suspect when you press 1 & 3 you'll see Console Addr = 31. In order to change the address, you'll need to power down the keypad. Check out paragraph 3 here: Your keypad is a 6139 rather than a 6160, but the process for addressing is the same. If you have multiple keypads, each will need a different address (16, 17, 18, and so on). Depending on the version of your new panel, you may need to enable any address above 16. Just finished installing my 20P, replacing a 20 year old 20HW that appeared to fail. I carefully labeled each wire and put them on the same terminal on the new board, checking to see that it made sense for the new installation manual for double-checking.

Double checked for good connections carefully - not unfamiliar territory for me. Ready to try programming it. When I plug the unit in the keypads give a tone and show shaded boxes across the display for about 1 second, then there is a sound like a relay click in the box and there is nothing useful. Pressing keys on the key pad make a tone, but it does not go into programming mode or show anything on the display.

Any suggestions on where to start? Thanks.I'll try power cycling the system next chance I get. Long story.I am actually the installer, sort-of. My father's company was an alarm contractor before he closed shop in 2008, and he passed away in 2012. We installed the system sometime around 2006/2007, I think (I was really just helping him with the cabling and stuff that he couldn't easily do - he did ALL of the programming. I know the installer code, I just can't remember if the programming can be downloaded.and/or how it would be downloaded.

My father did everything the old-fashioned way.not that its a bad thing, but it is time consuming and easy to make a mistake. That's why I was asking about downloading. It is Rev 5.2 if that helps.

Hi Frank, thanks for your response, unfortunately, by home is already build, and I am unable to pull the wires from the door frame etc. I also believe I have some wired to the smoke alarms. Basically I have a whole bunch of wires at demarc and no way of knowing which one goes where.

Could I use the continuity tester and start opening doors? Or could I use a resistance meter and start opening doors until I find the right one? Just wondering if there was a tool professionals used to work around this issue. I think nowadays most people just say forget it and go with the wireless system, which I find redundant in this case since my house was prewired.

Get a toner (aka tone generator), ideally one with a continuity tester built into it. From the peripheral locations connect the toner on the pair of wires using the alligator clips (must be on bare copper so strip the ends) and put it in tone mode. Go back to the centralized location (aka demarc) where all the wires are home run to. Use the wand (listening device that will make noise when it is touching the proper pair) to identify which pair your toner is connected to. Then label your wire with the location where the toner is setup.

To be sure this is the proper wire you can then strip the ends of that pair at the demarc and twist them together. Then go back to the toner and switch it to continuity mode (aka 'cont'). If the LED is lit then you have continuity and the circuit is shorted. This means it is definitely that pair and the sound is not bleeding over from another pair in the wall. You will get a feel for the toner and when the sound is loud and clear enough to the proper pair. You can look up some youtube videos on toner identification to get a better idea of how this is accomplished. I recommend the Fluke Pro 3000 Tone and Probe kit.

Good morning. After buying a vista 20(still in box) last august, its time to wire it in (to all the zones), 2 questions please- 1- why do you or when do you need to employ resistors? 2 - the 702 siren driver is just one unit i provided for, i would like to add a ELK sire driver to the far end of the house under the eve.AND mount the yellow thyristor flashing strobe to the front eve.Im going to need an additional power source I believe, if so, any tips?

All the wire is run and hidden well now (new build).thanks for any and all input. If you have a power outage, the battery kicks in. Once the battery runs the panel for awhile (with the power off), it drains the battery and eventually causes the low battery alert. As soon as power comes back on, the panel should recharge the battery so the alert goes away. Therefore, if you do have frequent power outages, it could be as simply as the panel is acting as expected.

If you get low battery alerts when there aren't long power outages, there could be something wrong with the internal charging circuit of the panel or you could have a bad battery. The alarm system control panel itself has a battery back up. You shouldn't need to have that plugged into a separate battery back up. Autodesk 3ds Max 2011 64 Bit Crack Download.

Also, the alarm system keypads are powered by that control panel so it should just be a matter of putting the router and the 7847i on a battery back up. Total Connect 2.0 is a newer interface with more detailed level of text/emails alerts. You can get alerts with the specific user that armed or disarmed and the specific zone name/number that was activated as opposed to generic messages on TC1.0. No,it's more: Running an alarm wire from the alarm box in the basement up to the second floor to plug in there. The router and 7847i (wired by cable from alarm box up) would be on the second floor. On the second floor I would have a UPS battery back up with the router and 7847i plugged in. If I can extend the alarm wire from the basement alarm box up to the second floor, then I could have just one UPS backup.

But not sure if the alarm box can be plugged in 45 feet away from the box. The control panel is on the main floor, but I don't think it has anything to do with this. Alternatively I could move the router and the 7847i into the basement next to the alarm box but it's an unfinished basement and a bit damp. What is your opinion, Also, is there a difference between 7847i connect 1.0 and connect 2.0?

Okay, just making sure. Yes, you can run a 4-conductor alarm wire from the panel to your router location so that you can mount the 7847i right by the router and connect it via Ethernet so that you only need one battery backup for the router as opposed to one for the router and then one for the wireless network device you'd plug into the 7847i to bridge the IP connection wirelessly. However, if you can fish that alarm wire, why not just fish an Ethernet cable so that you can install the 7847i at the panel? I am adding an IP communicator (7641i) to my Vista 20 P so it can be monitorred by Interent since I've cut out my home phone line. I have bought a UPS battery back up in case of power surge/cuts, but my router is on the 2nd floor and the alarm box is in the basement. My question is: can I fish an alarm wire from the basement to the second floor ( about 45 feet) to plug it into the UPS battery back up, upstairs with the router?

Rather than buy 2 UPS backups. Also is there an alternative to wireless monitorring instead of an IP communicator since that also involves wiring cable from the basement to the second floor? Maybe TP-LINK TL-WPA4220KIT ADVANCED 300Mbps Universal Wi-Fi Range Extender, Repeater, AV500 Powerline Edition, Wi-Fi Clone Button, 2 LAN Ports?